AXD Duct Type Axial Fan
Axial fan series for fresh air, exhaust and air transfer in industrial duct systems.
Product Features
- General
There are different model options in the range of 355–1250 mm.
- General
It can be produced as double speed and reversible.
- General
With aerofoil section and adjustable angle, the blades are produced by aluminium injection casting.
- General
Both sides are self-flanged without welding according to ISO 6580 / UNI-EUROVENT 1-2 standards.
- General
The fan casing is produced from hard steel and coated hot-dip galvanized as standard.
- General
It is suitable for operation in the temperature range -20°C / +55°C.
- Motor
The motor is IP55 protected, IE2/IE3 high efficiency, fully enclosed, with self-lubricating bearings and F insulation class.
- Motor
An external IP55 electrical junction box is provided outside the casing for easy electrical connection.
- Motor
It is 400V-50Hz as standard and suitable for use with a frequency converter.
Where is it used?
Model Technical Data
Nominal airflow alone is not a selection criterion. Verify the final model together with the required pressure and duty point in Fan Selection.
| Model | Nominal airflow | Voltage | Motor power | Speed | Current | Sound |
|---|---|---|---|---|---|---|
| AXD 35-4T-0,18 | 2,860 m³/h | 400V-50Hz | 0.12 kW | 1,360 rpm | 0.6 A | 67 dB(A) |
| AXD 40-4T-0,27 | 4,200 m³/h | 400V-50Hz | 0.18 kW | 1,360 rpm | 0.7 A | 72 dB(A) |
| AXD 40-4T-0,37 | 4,800 m³/h | 400V-50Hz | 0.25 kW | 1,360 rpm | 0.9 A | 72 dB(A) |
| AXD 45-4T-0,55 | 6,730 m³/h | 400V-50Hz | 0.37 kW | 1,370 rpm | 1.2 A | 75 dB(A) |
| AXD 50-4T-0,55 | 7,600 m³/h | 400V-50Hz | 0.37 kW | 1,370 rpm | 1.2 A | 74 dB(A) |
| AXD 50-4T-0,75 | 8,920 m³/h | 400V-50Hz | 0.55 kW | 1,430 rpm | 1.4 A | 76 dB(A) |
| AXD 56-4T-0,75 | 9,670 m³/h | 400V-50Hz | 0.55 kW | 1,430 rpm | 1.4 A | 79 dB(A) |
| AXD 56-4T-1 | 11,000 m³/h | 400V-50Hz | 0.75 kW | 1,430 rpm | 1.87 A | 77 dB(A) |
| AXD 56-4T-1,5 | 12,800 m³/h | 400V-50Hz | 1.1 kW | 1,440 rpm | 2.59 A | 78 dB(A) |
| AXD 63-4T-1 | 13,600 m³/h | 400V-50Hz | 0.75 kW | 1,430 rpm | 1.87 A | 79 dB(A) |
| AXD 63-4T-1,5 | 16,000 m³/h | 400V-50Hz | 1.1 kW | 1,440 rpm | 2.59 A | 80 dB(A) |
| AXD 63-4T-2 | 18,500 m³/h | 400V-50Hz | 1.5 kW | 1,440 rpm | 3.34 A | 81 dB(A) |
| AXD 35-2T-0,37 | 4,000 m³/h | 400V-50Hz | 0.25 kW | 2,770 rpm | 0.7 A | 78 dB(A) |
| AXD 35-2T-0,55 | 4,600 m³/h | 400V-50Hz | 0.37 kW | 2,770 rpm | 1.2 A | 80 dB(A) |
| AXD 35-2T-0,75 | 5,000 m³/h | 400V-50Hz | 0.55 kW | 2,770 rpm | 1.45 A | 82 dB(A) |
| AXD 35-2T-1 | 5,800 m³/h | 400V-50Hz | 0.75 kW | 2,880 rpm | 1.76 A | 82 dB(A) |
| AXD 40-2T-1 | 6,500 m³/h | 400V-50Hz | 0.75 kW | 2,880 rpm | 1.76 A | 85 dB(A) |
| AXD 40-2T-1,5 | 7,820 m³/h | 400V-50Hz | 1.1 kW | 2,870 rpm | 2.52 A | 85 dB(A) |
| AXD 40-2T-2 | 9,780 m³/h | 400V-50Hz | 1.5 kW | 2,870 rpm | 3.13 A | 87 dB(A) |
| AXD 45-2T-2 | 11,000 m³/h | 400V-50Hz | 1.5 kW | 2,870 rpm | 3.13 A | 88 dB(A) |
| AXD 45-2T-3 | 12,100 m³/h | 400V-50Hz | 2.2 kW | 2,875 rpm | 4.45 A | 88 dB(A) |
| AXD 45-2T-4 | 15,000 m³/h | 400V-50Hz | 3 kW | 2,900 rpm | 5.77 A | 91 dB(A) |
| AXD 50-2T-3 | 14,000 m³/h | 400V-50Hz | 2.2 kW | 2,875 rpm | 4.45 A | 86 dB(A) |
| AXD 50-2T-4 | 15,600 m³/h | 400V-50Hz | 3 kW | 2,900 rpm | 5.77 A | 89 dB(A) |
| AXD 50-2T-5,5 | 18,200 m³/h | 400V-50Hz | 4 kW | 2,910 rpm | 7.44 A | 91 dB(A) |
| AXD 56-2T-3 | 14,000 m³/h | 400V-50Hz | 2.2 kW | 2,875 rpm | 4.45 A | 97 dB(A) |
| AXD 56-2T-4 | 17,600 m³/h | 400V-50Hz | 3 kW | 2,900 rpm | 5.77 A | 95 dB(A) |
| AXD 56-2T-5,5 | 20,300 m³/h | 400V-50Hz | 4 kW | 2,910 rpm | 7.44 A | 94 dB(A) |
| AXD 56-2T-7,5 | 23,500 m³/h | 400V-50Hz | 5.5 kW | 2,910 rpm | 10.5 A | 93 dB(A) |
| AXD 63-2T-7,5 | 24,500 m³/h | 400V-50Hz | 5.5 kW | 2,910 rpm | 10.5 A | 95 dB(A) |
| AXD 63-2T-10 | 28,000 m³/h | 400V-50Hz | 7.5 kW | 2,920 rpm | 14 A | 94 dB(A) |
| AXD 71-2T-7,5 | 28,500 m³/h | 400V-50Hz | 5.5 kW | 2,910 rpm | 10.5 A | 96 dB(A) |
| AXD 71-2T-10 | 35,000 m³/h | 400V-50Hz | 7.5 kW | 2,920 rpm | 14 A | 96 dB(A) |
| AXD 71-2T-15 | 40,000 m³/h | 400V-50Hz | 11 kW | 2,940 rpm | 19.6 A | 98 dB(A) |
| AXD 71-2T-20 | 41,300 m³/h | 400V-50Hz | 15 kW | 2,940 rpm | 26.5 A | 101 dB(A) |
| AXD 63-4T-3 | 20,000 m³/h | 400V-50Hz | 2.2 kW | 1,445 rpm | 4.83 A | 84 dB(A) |
| AXD 71-4T-3 | 23,400 m³/h | 400V-50Hz | 2.2 kW | 1,445 rpm | 4.83 A | 87 dB(A) |
| AXD 71-4T-4 | 26,600 m³/h | 400V-50Hz | 3 kW | 1,445 rpm | 6.4 A | 88 dB(A) |
| AXD 80-4T-4 | 30,000 m³/h | 400V-50Hz | 3 kW | 1,445 rpm | 6.4 A | 88 dB(A) |
| AXD 80-4T-5,5 | 34,100 m³/h | 400V-50Hz | 4 kW | 1,450 rpm | 8.15 A | 89 dB(A) |
| AXD 80-4T-7,5 | 38,500 m³/h | 400V-50Hz | 5.5 kW | 1,455 rpm | 11 A | 90 dB(A) |
| AXD 90-4T-5,5 | 38,500 m³/h | 400V-50Hz | 4 kW | 1,450 rpm | 8.15 A | 87 dB(A) |
| AXD 90-4T-7,5 | 45,800 m³/h | 400V-50Hz | 5.5 kW | 1,455 rpm | 11 A | 90 dB(A) |
| AXD 90-4T-10 | 52,000 m³/h | 400V-50Hz | 7.5 kW | 1,460 rpm | 15 A | 92 dB(A) |
| AXD 100-4T-7,5 | 49,500 m³/h | 400V-50Hz | 5.5 kW | 1,455 rpm | 11 A | 95 dB(A) |
| AXD 100-4T-10 | 58,000 m³/h | 400V-50Hz | 7.5 kW | 1,460 rpm | 15 A | 95 dB(A) |
| AXD 100-4T-15 | 66,500 m³/h | 400V-50Hz | 11 kW | 1,470 rpm | 21.2 A | 95 dB(A) |
| AXD 100-4T-20 | 68,500 m³/h | 400V-50Hz | 15 kW | 1,470 rpm | 28.3 A | 95 dB(A) |
| AXD 112-4T-15 | 61,000 m³/h | 400V-50Hz | 11 kW | 1,470 rpm | 21.2 A | 99 dB(A) |
| AXD 112-4T-20 | 74,000 m³/h | 400V-50Hz | 15 kW | 1,470 rpm | 28.3 A | 99 dB(A) |
| AXD 112-4T-25 | 86,500 m³/h | 400V-50Hz | 18.5 kW | 1,470 rpm | 35.6 A | 98 dB(A) |
| AXD 112-4T-30 | 92,500 m³/h | 400V-50Hz | 22 kW | 1,470 rpm | 42.5 A | 98 dB(A) |
| AXD 125-4T-20 | 73,000 m³/h | 400V-50Hz | 15 kW | 1,470 rpm | 28.3 A | 97 dB(A) |
| AXD 125-4T-25 | 83,000 m³/h | 400V-50Hz | 18.5 kW | 1,470 rpm | 35.6 A | 98 dB(A) |
| AXD 125-4T-30 | 93,200 m³/h | 400V-50Hz | 22 kW | 1,470 rpm | 42.5 A | 99 dB(A) |
| AXD 125-4T-40 | 112,000 m³/h | 400V-50Hz | 30 kW | 1,480 rpm | 53.2 A | 100 dB(A) |
Source: Vensis Fan Selection Suite. Product and motor configurations must be verified for the ordered model.
Frequently Asked Technical Questions
What is AXD?
Axial fan series for fresh air, exhaust and air transfer in industrial duct systems. Sub-models in this product family are listed on this page from the Vitlo product database.
How do I select the right model?
Along with the required airflow, system pressure, operating conditions and any special safety requirements must be defined. The duty point should then be verified in Fan Selection.
Why are the technical table and selection tool used together?
The product page provides clear technical context, while Fan Selection verifies the model and duty point.
Let’s select the right fan for your project.
Share airflow, pressure and application conditions; we will evaluate the appropriate series and model.