AXW/ATEX Wall-Mounted Exproof Fan
Wall-mounted axial exproof fan series for ventilation applications in explosive atmospheres.
Product Features
- General
There are different model options in the range of 355–1000 mm.
- General
It has a square plate and wire mesh and is ex-proof as a complete device.
- General
With aerofoil section and adjustable angle, the blades are produced by aluminium injection casting.
- General
The fan casing is produced from hard steel and electrostatic powder coated as standard.
- General
An aluminium plate in accordance with EN 14986:2017 is applied between the fan and the casing.
- General
It is suitable for operation in the temperature range -20°C / +55°C.
- Motor
The motor is IP65 protected, IE2/IE3 high efficiency, fully enclosed, with self-lubricating bearings and F insulation class.
- Motor
Depending on model, 4, 6 and 8 pole motor options are available with II 2G EEx d/e IIB/IIC T4-T3 protection ratings.
- Motor
It is 400V-50Hz as standard and suitable for use with a frequency converter.
Where is it used?
Model Technical Data
Nominal airflow alone is not a selection criterion. Verify the final model together with the required pressure and duty point in Fan Selection.
| Model | Nominal airflow | Voltage | Motor power | Speed | Current | Sound |
|---|---|---|---|---|---|---|
| AXW/ATEX 35-4T-0,18 | 2,860 m³/h | 400V-50Hz | 0.12 kW | 1,380 rpm | 0.65 A | 67 dB(A) |
| AXW/ATEX 40-4T-0,27 | 4,200 m³/h | 400V-50Hz | 0.18 kW | 1,380 rpm | 0.75 A | 72 dB(A) |
| AXW/ATEX 40-4T-0,37 | 4,800 m³/h | 400V-50Hz | 0.25 kW | 1,420 rpm | 1 A | 72 dB(A) |
| AXW/ATEX 45-4T-0,55 | 6,730 m³/h | 400V-50Hz | 0.37 kW | 1,425 rpm | 1.35 A | 75 dB(A) |
| AXW/ATEX 50-4T-0,55 | 7,600 m³/h | 400V-50Hz | 0.37 kW | 1,425 rpm | 1.35 A | 74 dB(A) |
| AXW/ATEX 50-4T-0,75 | 8,920 m³/h | 400V-50Hz | 0.55 kW | 1,410 rpm | 1.5 A | 76 dB(A) |
| AXW/ATEX 56-4T-0,75 | 9,670 m³/h | 400V-50Hz | 0.55 kW | 1,410 rpm | 1.5 A | 79 dB(A) |
| AXW/ATEX 56-4T-1 | 11,000 m³/h | 400V-50Hz | 0.75 kW | 1,430 rpm | 2.1 A | 77 dB(A) |
| AXW/ATEX 56-4T-1,5 | 12,800 m³/h | 400V-50Hz | 1.1 kW | 1,440 rpm | 2.7 A | 78 dB(A) |
| AXW/ATEX 63-4T-1 | 13,600 m³/h | 400V-50Hz | 0.75 kW | 1,430 rpm | 2.1 A | 79 dB(A) |
| AXW/ATEX 63-4T-1,5 | 16,000 m³/h | 400V-50Hz | 1.1 kW | 1,440 rpm | 2.7 A | 80 dB(A) |
| AXW/ATEX 63-4T-2 | 18,500 m³/h | 400V-50Hz | 1.5 kW | 1,440 rpm | 3.45 A | 81 dB(A) |
| AXW/ATEX 63-4T-3 | 20,000 m³/h | 400V-50Hz | 2.2 kW | 1,440 rpm | 4.66 A | 84 dB(A) |
| AXW/ATEX 71-4T-3 | 23,400 m³/h | 400V-50Hz | 2.2 kW | 1,440 rpm | 4.66 A | 87 dB(A) |
| AXW/ATEX 71-4T-4 | 26,600 m³/h | 400V-50Hz | 3 kW | 1,440 rpm | 6.27 A | 88 dB(A) |
| AXW/ATEX 80-4T-4 | 30,000 m³/h | 400V-50Hz | 3 kW | 1,440 rpm | 6.27 A | 88 dB(A) |
| AXW/ATEX 80-4T-5,5 | 34,100 m³/h | 400V-50Hz | 4 kW | 1,450 rpm | 8.5 A | 89 dB(A) |
| AXW/ATEX 80-4T-7,5 | 38,500 m³/h | 400V-50Hz | 5.5 kW | 1,460 rpm | 10.6 A | 90 dB(A) |
| AXW/ATEX 90-4T-5,5 | 38,500 m³/h | 400V-50Hz | 4 kW | 1,440 rpm | 8.5 A | 87 dB(A) |
| AXW/ATEX 90-4T-7,5 | 45,800 m³/h | 400V-50Hz | 5.5 kW | 1,460 rpm | 10.6 A | 90 dB(A) |
| AXW/ATEX 90-4T-10 | 52,000 m³/h | 400V-50Hz | 7.5 kW | 1,460 rpm | 14.4 A | 92 dB(A) |
| AXW/ATEX 100-4T-7,5 | 49,500 m³/h | 400V-50Hz | 5.5 kW | 1,460 rpm | 10.6 A | 95 dB(A) |
| AXW/ATEX 100-4T-10 | 58,000 m³/h | 400V-50Hz | 7.5 kW | 1,460 rpm | 14.4 A | 95 dB(A) |
| AXW/ATEX 100-4T-15 | 66,500 m³/h | 400V-50Hz | 11 kW | 1,470 rpm | 21.2 A | 95 dB(A) |
Source: Vensis Fan Selection Suite. Product and motor configurations must be verified for the ordered model.
Frequently Asked Technical Questions
What is AXW/ATEX?
Axial exproof fan series for wall-mounted ventilation in explosive atmospheres. Sub-models in this product family are listed on this page from the Vitlo product database.
How do I select the right model?
Along with the required airflow, system pressure, operating conditions and any special safety requirements must be defined. The duty point should then be verified in Fan Selection.
Why are the technical table and selection tool used together?
The product page provides clear technical context, while Fan Selection verifies the model and duty point.
Let’s select the right fan for your project.
Share airflow, pressure and application conditions; we will evaluate the appropriate series and model.